16.00  COMPUTERISED LABORATORY
          

Technical data and measurements availables      See   chapter 15.40   

 

CONFORMITY TESTS AVAILABLE
 
Step-stress test, Din 44874
   
The purpose of the test is the determination of the Burning Index (B.I.) of a heating element.
 
 
Test of the 200 ageing cycles, Din 44874
   
The purpose of the test is to establish if, after 200 uninterrupted working cycles, the leakage current of a
    heating element has been subjected to alterations and to what degree.
 
 
Test of the 15 cycles in overload conditions, as per CEI 61-150 norm, VDE 0720, IEC 335-1, NF 73200
   
The international norm foresees that a heating element, after the test of the 15 cycles in overload
   conditions at 1.27 times the Nominal Power, does not present anomalies at the end of the test.
 
 
 
Additional tests available 
 
Test of uprated power and measurement of the time to failure
   
This is an alternative test to the step-stress test in the cases where the maximum applicable power is not
   enough to burn the heating element (heating element with low specific load).
 
 
Initial failure test (infant mortality)
   
The purpose of the test is to verify that no heating element of a batch, which is being dispatched or is
   arriving, has defects, which can come out in the first working cycles.
 
 
Uprated power test at a defined time and verification of survival
   
This test subjects a certain number of heating elements (Ex. 3) to a defined period of ON working
   (Ex. from 1 to 3 hours) with a higher power than the nominal one (Ex. 2 nominal power) and to verify that
   at the end of the test the heating elements are still working and/or the values are in the expected
   tolerances.
 
 
Uprated power test with defined cycles and verification of survival
   
This test subjects a certain number of heating elements (Ex. 3) to a defined number of ON/OFF cycles    (Ex. from 20 to 100) with a higher power than the nominal one (double nominal power).
   In addition to the number of set cycles, the system will automatically start an ON cycle for a defined time
   with nominal power.
 
 
 
Technological tests 
 
Test of the 200 ageing cycles with continuous test
   
This test is wider than test (Ex. 2), as it follows the course of the leakage stationary current within 200
   cycles, determining 15 intermediate readings.
 
 
Test of on/off cycles in step-stress modes
   
The purpose of the test is to cause the failure of the heating element in a short time by increasing
   simultaneously the specific load of the spiral tube and the time of ON/OFF cycle.
 
 
Interrupted step-stress test
   
The purpose of the test is to subject a certain number of heating elements, all of the same model and
   production batch, to increasing power steps, to establish at which power the degradation of the electric
   characteristics occurs.
 
 
Uprated power test and measurement of the cycles to failure
   
The Accelerated Mean Life, which is determined in working conditions that are more exaggerated than
   the normal ones, is a parameter that may be correlated to the mean useful life, which is determined in the
   real working conditions.
 
 
Useful life test to failure
   
The purpose of the test is to determine the Mean Useful Life of a heating element in working conditions
   that are as close as possible to the everyday usage.
 
 
Test of the accelerated mean life of the heating elements at a specific load lower than 3w/cm2
   
The purpose of the test is to determine the Mean Useful Life of a heating element in more accelerated
   conditions of heat exchange, to reduce the testing time.
 
 
Test of the accelerated mean life of the heating elements with removal of reduced heat
  
 The purpose of the test is to determine the Mean Useful Life of a heating element in conditions that are
   as close as possible to the everyday usage, with removal of air forced heat.
 
 
Test of the accelerated mean life for heating elements with silicone sealing
   
The purpose of the test is to quickly verify if the process of sealing with silicone sealing products is
   adequate to preserve the electric properties of the heating element.
 
 
Test of the accelerated mean life for heating elements with silicone sealing at high temperature
   It is the same as test 15, with the difference that, being the testing conditions in the humidostatic chamber
   worse than in the preceding test, the acceleration factor AF will result numerically greater and the testing
   times shorter.
 
 
Test of the accelerated mean life of heating elements in function of the electric insulation at temperature (85±2)°c and r.h. (85±2)%
   The purpose of the test is to quickly verify the average time within which a normal heating element goes
   over the lower threshold of the electric insulation value.
   The test consists in verifying the values of insulation and leakage current in the testing period on heating
   elements that have remained in a humidostatic chamber.
 
 
Test of the accelerated mean life of heating elements subjected to heat shocks
   The purpose of the test is to subject the heating elements to heat cycles, which are very rapid both as
   regards power and duration, to obtain a fast check of the qualitative level of a batch of heating elements.
   The heating elements (min. 5) are led to failure and burning.
 
 
Test for the determination of the acceleration factor (AF) in accelerated tests
  
 The purpose of the test is to determine the acceleration factor AF to correlate the Accelerated Mean Life
   with the Useful Mean Life that is the real one, without accelerations.
 

   NOTE: You can require technical specifications for each individual test.